Knee Point Voltage of Current Transformers:
Knee point voltage parameter is very important for Protection current transformers especially for Class-PS that is Special purpose current transformers.
First of all, we will see how Protection class CTs differ from Metering Class CTs.
There are two basic types of Current transformers metering and protection. The basic difference between the two is, for measurement CTs the limits are well defined whereas protection CTs have to operate over a wide range of currents. So their characteristics must be different from measuring CTs.
Measurement CTs require good accuracy up to 120%. They require low level saturation to protect meters, so they made with Nickel-Iron alloy core with low exciting current and knee point at low flux density.
Protection CTs accuracy is not important as measurement CTs. They require accuracy up to many times rated current, so they made with Grain oriented silicon steel with high saturation flux density.
Details of Knee Point Voltage:
Every Protection class CT Name plate contains details of Knee point voltage as shown in below figure. The name plate is for 3-Core CT with middle taps. For this CT the knee point voltage for PS-Class core is Vk >= 120V for 3S1-3S3 winding and Vk >=60V for 3S1-3S2 winding. Also the excitation current should less than or equal to 100mA at VK/4 for anyone of Core-3 windings.
Current Transformers magnetization curve helps to understand the knee point voltage.
Magnetization curve of Current Transformers:
This curve is generally plotted in secondary volts vs exciting current measured in secondary. From this curve we can easily find the magnitude of exciting current required to produce the given amount of CT secondary voltage.
The magnetization or excitation curve divided into four regions.
1. From origin to ankle point
2. From ankle point to knee
3. Knee region
4. Saturation region
Knee point is simply defined as,
“Where a 10% increase in flux density cause 50% increase to exciting ampere-turns”.
The regions are shown in figure below.
- The measuring current transformer has the flux density in the region of ankle-point only.
- Protection current transformer generally operates over-working flux density extending from the ankle-point to the knee-region of above.
Prior to saturation, the flux density in core is proportional to ampere-turns. On reaching saturation, magnetizing inductance becomes low and the total primary current is utilized in exciting the core alone and, therefore, the secondary output of CT disappears. (There is no secondary current at all even primary current present).
The saturation continues till the primary transient current is reduced below saturation level. If CT operating in saturation zone, the CT behaves an open circuited.
Effect of saturation on performance of CT:
It is difficult to avoid saturation during short circuit condition. The effect of saturation is the reduced output, hence reduced speed of over-current relays. In differential relays the saturation disturbs the balance and stability of protection is affected. If CT exposed to higher primary currents for prolonged times Permanent saturation occurs and hence the CT can’t be used further.
Causes of saturation:
Short-circuit current has d.c component flowing for several tens of milliseconds. The d.c component causes saturation of the CT core resulting in error. The exciting current is consumed by core and the output of CT is reduced to almost zero.
How to avoid saturation effect?
Nowadays the measuring times of protective relays reduced to the transient state.
Also CTs with gapped cores are used to avoid saturation during prolonged short-circuit currents. Such CTs are used for high speed distance protection of lines.
Verification of Knee Point Voltage of CT:
Current transformers knee point voltage can be obtained from the Name plate details of Protection Class CTs. However, it is to be verified during commissioning of new CTs.
To verify the Vk value of a given Current Transformer, the process is as follows.
Exciting currents is measured for several secondary e.m.fs. This is accomplished by applying voltage to the secondary winding, the primary and other windings being open circuited. The connections are shown in figure.
Let us, consider an example CT of PS class used for Differential Protection with the following Knee point values.
VK ≥ 30 V
Ie ≤ 30mA @ Vk/2
To verify the knee point voltage, increase CT secondary applied voltage gradually until reaching knee point.
The obtained readings are as follows.
If we recall the definition of Knee point voltage, the value of voltage at which when the applied voltage is increased by 10 percent, causes the exciting current to increase by 50 percent.
At 36V applied voltage the current raises abruptly to the value of 0.015 Amps. This rise is from 32V to 36V (voltage increased by 10%) and current increased from 0.010A to 0.015 (current increased by 50%). Hence the knee point voltage VK of the given current transformer is at 32V.
Also the other condition at Vk/2 that is at 16V the current value should be less than or equal to 30mA also verified from the above test results.
Illustration of knee point is good.
Please Note: Current shown in above chart at Vk/2 is 3 mA not 30 mA please check the decimal point position.
Hi Shankar..As per the Name plate it is 30mA only. But practical result is some where between 4-5mA even it is less than 30mA at Vk/2, which is the desired condition. Hope you got it.
Hi
Thanks for info but for PX CT transformer, would a CT with a magnetizing current of 160mA at knee point of 85V be suitable for Low Impedance REF? If not how high should the magnetizing current should be?
Hi Kris,
If the existing equipment is of such a nature that the same ratios are not available for both phase and neutral CTs, you should use low-impedance REF protection, because this type of protection can handle different CT ratios for phase and neutral CTs.
This is the main advantage of low-impedance REF protection is the fact that the CT ratios for the phase CTs and neutral CTs do not have to be the same.
Low impedance REF is based on comparing the vector sum of the phase currents of the transformer winding to the neutral point current.
Because of the inherently unstable nature of the low impedance REF element, it may misoperate during external faults, especially in the case of faults not involving the earth as phase-to-phase and three-phase faults, when one of the phase CTs saturates.
It is a requirement that the neutral CT has a lower ratio than the line CTs to provide better earth fault sensitivity.
Thanks for reply and its very informative,
But sorry if I don’t understand, but how does higher or lower magnetisation current of CT affect Low Impedance REF?
Additionally, high magnetising current relates to high CT error. Would it be a problem for Low Imp REF?